Filtering ceiling TL-PM 09
Xem cỡ ảnh lớn
Filtering ceiling TL-PM 09
Country of origin
Hanoi, Viet Nam
Product name
Filtering ceiling TL-PM-09
Model
TL-PM 09
MOQ
1 Set/Sets
Port:
Haiphong
Packing details
Wooden Pallet, Containers
Delivery time
15 days
Payment term
L/C, T/T
Supply ability
100 Set/Sets per month

Filtering ceiling for ISO 5 rooms according to 14644-1 for operation theatres risk 3 or 4

Advantages:

● France Air commits the airtightness of the system by placing a plenum and filters.

● Very simple and riliable filter tightening system.

● Diffusion grille generating, on the whole surface to protect, a unidirectional flow as described in the Norm NF S 90-351.

8 range

● 7 standard dimensions: from 1390 x 1330 to 2975 x 2060.

● Supplied air flow from 1330 m3/h to 8000 m3/h.

● Standard height: 450 mm.

● Filtration V.H.E: H14 or U15 in standardised heights (thickness 68 mm).

 Application:

● Filtering ceiling with unidirectional flow enabling the obtaining of ISO 5 according to te norm EN ISO 14644-1 at the required air renewable rate.

● Sterile room, aseptic covers.

● Hospitals and pharmacteutic industries...

● Wall version for horizontal flow.

 Picture2

Construction/ composition:

● Plenum:

- Stainless steel sheet (10/10th) with white epoxy paint RAL 9010.

- Pressure tap (diam. 3 mm) on one of the vertical sides.

- Return of 25 mm at inferior part for fitting of false-seiling.

- Angle bracket supplied with fixing holes (diam. 10 mm every 60 cm) at superior part for fixing of the slap.

- Lateral air inlet made of a rigid sleeve (height 200 mm– depth: 150 mm).

● Support frames for filters:

- Stainless steel sheet (15/10th) with white epoxy paint RAL 9010.

- Forming at low part of the plenum a self-supporting frame on which the filters are assembled.

- Gasket surface perfectly airtight and flat, withour possibility of leaks in angles.

- Assembly of frames between themselves and frame/plenum assembly done at factory.

- Contains 6 tightening points for the filters. The filters tightening  is done with stainless steel pivoting feet 1/4 turn.

- Contains 4 fixing insets for grilles or the maskings.

● Filters “Very high efficiency” (not included):

- Filtering cells, standard size: 3.6 - 9.6 and 12.6.

- Efficiency: H14 or U15.

● Diffusion grilles:

- Stainless steel sheet (performation rate: 40%) with white epoxy rate RAL 9010.

- Ensures a regular air diffusion, withour stopping or dead zone.

 

 


Các sản phẩm cùng loại

Air supply system for operating room TL - PM 05

Operating room

Operating room door

Operating room

Filtering ceiling with recycled air for operation rooms

Operating room purifier TL-PM-01

Positive pressure sterillization filtration system

Laminar Air Flow for Medical Application

Operating room

Operating room